Volkswagen Tiguan Service and Repair Manual: Checking with Expansion Valve, Receiver/Dryer and A/C Compressor
Regulator Valve -N280-, Externally Regulated A/C Compressor
Specified Values
Note
- Connecting service station.
- Observe test requirements.
- Bring engine speed up to 2000 RPM.
- Pay attention to the A/C service station pressure gauge.
Note
High-pressure side:
Increasing from initial pressure (when connecting pressure gauges) to 20 bar
(290 psi).
Low-pressure side:
Decreasing from initial pressure (when connecting pressure gauges) to the
value in the graph.
- Low pressure (measured at service connection) in bar (psi) absolute
- Control current for A/C Compressor Regulator Valve -N280-.
- Permissible tolerance range
Note
- Under unfavorable conditions (very high ambient temperatures, high
humidity), pressure on high-pressure side may increase to max. 29 bar (421
psi).
- The control current -B- is shown in the
measured value block.
- The high pressure measured from the High Pressure Sensor -G65- is not
shown in the measured value block.
- Low pressure settles as a function of control current for A/C Compressor
Regulator Valve -N280- within compressor output range in tolerance range.
- Under unfavorable conditions (very high ambient temperatures, high
humidity), compressor output may not always be sufficient to attain the
specified value.
- The specified operating current for the regulator valve must be greater
than 0.3 A in order to ensure reliable valve activation.
- In the setting "maximum cooling output" control current is regulated to
approximately 0.65 A up to 0.8 A (vehicle specific, displayed in measured
value block).
- At absolute pressure, 0 bar/psi corresponds to absolute vacuum. Normal
ambient pressure corresponds to 1 bar (14.5 psi) absolute pressure. 0 bar/psi
pressure corresponds to an absolute pressure of 1 bar (14.5 psi) on most
pressure gauges (indicated by 1 bar (14.5 psi) below 0 bar/psi).
Possible deviation from specification |
Possible cause of fault |
Corrective
action |
- High pressure remains constant or increases only slightly (above
pressure with engine stopped).
- Low pressure quickly drops to value in graph or below.
- Required cooling output is not attained
|
- Activation of A/C Compressor Regulator Valve -N280- is faulty.
- Not enough refrigerant in refrigerant circuit
|
- Check activation of A/C Compressor Regulator Valve -N280-.
- Localize the leak with leak detector and eliminate
- Charge the refrigerant circuit.
|
- High pressure normal.
- Low pressure in line with value in graph.
- Required cooling output is not attained
|
|
|
- High pressure normal.
- Low pressure too low (see graph).
- Required cooling output is not attained
|
- Not enough refrigerant in refrigerant circuit
|
- Extract refrigerant from the refrigerant circuit
- If quantity of refrigerant extracted is substantially less than
specified capacity.
- Localize leak with leak detector and eliminate.
- Charge the refrigerant circuit.
- Repeat the test.
- If quantity of refrigerant extracted roughly corresponds to
specified capacity
|
|
|
- Replace expansion valve
- Charge the refrigerant circuit.
- Repeat the test.
|
Note
- If no malfunction is found with this complaint, flush (clean)
refrigerant circuit with refrigerant R134a. If that is not possible in this
workshop, flush the refrigerant circuit with compressed air and remove
moisture with nitrogen.
- Check measured values from Evaporator Vent Temperature Sensor -G263- or
Evaporator Temperature Sensor -G308- and activation of A/C Compressor
Regulator Valve -N280-. If the measured value of the Evaporator Vent
Temperature Sensor -G263- or Evaporator Temperature Sensor -G308- is not OK,
the evaporator can ice up or the cooling output will not be reached.
- If the function of the air conditioning system is not OK when the test
is repeated after replacing expansion valve, re-install old expansion valve
and flush refrigerant circuit with compressed air and nitrogen. Then replace
A/C compressor and receiver/dryer.
- With this malfunction, evaporator may ice up although quantity of
refrigerant in circuit is OK.
- If expansion valve is malfunctioning (permanently closed or does not
open sufficiently), A/C Compressor Regulator Valve -N280- is actuated to
maximum output and low pressure drops to value in graph or below (compressor
draws off refrigerant from low-pressure side). Because refrigerant cannot
flow through the expansion valve, the correct cooling output cannot be
reached. The high pressure may not increase or may only increase slightly.
Possible deviation from specification |
Possible cause of fault |
Corrective
action |
- High pressure only increases slightly above pressure with engine
stopped.
- Low pressure drops only slightly.
- Required cooling output is not attained
|
- Activation of A/C Compressor Regulator Valve -N280- is faulty.
|
- Check activation of A/C Compressor Regulator Valve -N280-.
|
|
|
- Extract refrigerant circuit.
- Flush (clean) refrigerant circuit.
- Replace A/C compressor.
- Charge the refrigerant circuit.
|
- High pressure increases above specification.
- Low pressure quickly drops to value in graph or below.
- Required cooling output is not attained
|
- Activation of A/C Compressor Regulator Valve -N280- is faulty.
|
- Check activation of A/C Compressor Regulator Valve -N280-.
|
|
- Constriction or obstruction in refrigerant circuit
|
- Run hand over refrigerant circuit to check for differences in
temperature
- If difference in temperature is found at one component:
- Replace the hose or pipe if kinked or constricted.
- In the event of an obstruction, flush refrigerant circuit
with compressed air and nitrogen
- Charge the refrigerant circuit.
- Repeat the test.
- If no malfunction can be found:
- Flush (clean) refrigerant circuit.
- Charge the refrigerant circuit.
- Repeat test if function is not OK.
|
|
|
- Extract refrigerant circuit.
- Replace expansion valve and receiver/dryer
- Charge the refrigerant circuit.
|
Note
- With this malfunction, evaporator may ice up although quantity of
refrigerant in circuit is OK.
- If expansion valve is malfunctioning (permanently closed or does not
open sufficiently), A/C Compressor Regulator Valve -N280- is actuated to
maximum output and low pressure drops to value in graph or below (compressor
draws off refrigerant from low-pressure side). Because refrigerant cannot
flow through the expansion valve, the correct cooling output cannot be
reached. The high pressure may not increase or may only increase slightly.
Possible deviation from specification |
Possible cause of fault |
Corrective
action |
- High and low pressure normal at first, after some time high
pressure increases above specification.
- after some time, low pressure decreases to graph value or lower.
- Required cooling output is no longer attained.
|
- Activation of A/C Compressor Regulator Valve -N280- is faulty.
|
- Check activation of A/C Compressor Regulator Valve -N280-.
|
- High pressure and lower pressure normal first, after a long
period of driving, the low pressure falls below the specified value
(evaporator iced up).
|
- Moisture in refrigerant circuit
|
- Extract refrigerant circuit.
- Flush refrigerant circuit with compressed air and nitrogen.
- Replace receiver/dryer with dryer.
- Evacuate refrigerant circuit for at least 3 hours.
- Charge the refrigerant circuit.
- Repeat test, if function is not OK
- Flush (clean) refrigerant circuit.
- Charge the refrigerant circuit.
- Repeat the test.
|
Note
- If this complaint occurs after a long operating time or only
sporadically (the low pressure falls under the specified value and the
evaporator ices up), replacing the dryer (installed in the receiver/dryer)
is sufficient. The quantity of refrigerant oil should be adjusted.
Refrigerant circuit is then to be evacuated for at least 3 hours.
- First, it is not necessary to flush the refrigerant circuit with
compressed air and nitrogen in case of this complaint because generally only
a small amount of moisture is in the system and this can be removed by a
long evacuation.
- With this malfunction, evaporator may ice up although quantity of
refrigerant in circuit is OK.
Possible deviation from specification |
Possible cause of fault |
Corrective
action |
- High pressure normal, low pressure too low (see graph), the
necessary cooling output is not reached.
|
- Activation of A/C Compressor Regulator Valve -N280- is faulty.
|
- Check activation of A/C Compressor Regulator Valve -N280-.
|
|
|
- Extract refrigerant circuit
- Flush (clean) refrigerant circuit.
- Replace expansion valve and receiver/dryer
- Charge the refrigerant circuit.
- Repeat test if function is not OK.
- Replace the A/C compressor.
|
|
|
- Extract refrigerant circuit.
- Flush (clean) refrigerant circuit.
- Replace the A/C compressor.
- Charge the refrigerant circuit.
- Repeat the test.
|
Note
- For the malfunction "high pressure normal, low pressure too low", note
the following: faulty, the evaporator can ice up or the cooling output is
not reached.
- With this malfunction, evaporator may ice up although quantity of
refrigerant in circuit is OK.
- Check measured values from Evaporator Vent Temperature Sensor -G263- or
Evaporator Temperature Sensor -G308- and activation of A/C Compressor
Regulator Valve -N280-. If the measured value of the High Pressure Sensor
-G65- is faulty, the evaporator can ice up or the cooling output is not
reached.
- If the problem is with the A/C Compressor Regulator Valve -N280-
(regulating valve is not actuated but compressor operates nevertheless),
refrigerant circuit does not have to be flushed. With this malfunction,
replacing the A/C compressor is sufficient (adjust refrigerant oil quantity
in new A/C compressor).
- If expansion valve is malfunctioning (permanently closed or does not
open sufficiently), A/C Compressor Regulator Valve -N280- is actuated to
maximum output and low pressure drops to value in graph or below (compressor
draws off refrigerant from low-pressure side). Because refrigerant cannot
flow through the expansion valve, the correct cooling output cannot be
reached. The high pressure may not increase or may only increase slightly.
Possible deviation from specification |
Possible cause of fault |
Corrective
action |
- High pressure normal or too high.
- Low pressure too high (see graph).
- A/C compressor noise (particularly after switch-on).
- Required cooling output is not attained
|
- Activation of A/C Compressor Regulator Valve -N280- is faulty.
- Too much refrigerant in the circuit.
|
- Check activation of A/C Compressor Regulator Valve -N280-.
- Extract refrigerant from the refrigerant circuit
- If quantity of refrigerant extracted roughly corresponds to
specified capacity:
- Replace the A/C compressor
- If quantity of refrigerant extracted is substantially greater
than specified capacity
- Charge the refrigerant circuit.
- Repeat the test.
|
|
- To much refrigerant oil in the circuit.
|
- Discharge the refrigerant circuit.
- If quantity of refrigerant extracted roughly corresponds to
specified capacity:
- Flush (clean) refrigerant circuit.
- Charge the refrigerant circuit.
- Repeat the test.
|
|
|
- Discharge the refrigerant circuit.
- Replace expansion valve and receiver/dryer
- Charge the refrigerant circuit.
- Repeat test if function is not OK.
- Replace the A/C compressor.
|
|
|
- Discharge the refrigerant circuit.
- Flush (clean) refrigerant circuit.
- Replace the A/C compressor.
- If quantity of refrigerant extracted is substantially greater
than specified capacity:
- Charge the refrigerant circuit.
- Repeat the test.
|
Note
- If the problem is with the A/C Compressor Regulator Valve -N280-
(regulating valve is not actuated but compressor operates nevertheless),
refrigerant circuit does not have to be flushed. With this malfunction,
replacing the A/C compressor is sufficient (adjust refrigerant oil quantity
in new A/C compressor).
- Overfilling with refrigerant oil can occur if, for example, the
compressor has been replaced without adjusting the quantity of refrigerant
oil.
- If the A/C compressor is not replaced, the refrigerant oil should be
drained from the A/C compressor via the oil drain plug. Out of the entire
quantity of refrigerant oil, 50 grams should be put in the A/C compressor
and the rest in the refrigerant circuit. Refer to vehicle-specific repair
manual.
- If expansion valve is malfunctioning (permanently closed or does not
open sufficiently), A/C Compressor Regulator Valve -N280- is actuated to
maximum output and low pressure drops to value in graph or below (compressor
draws off refrigerant from low-pressure side). Because refrigerant cannot
flow through the expansion valve, the correct cooling output cannot be
reached. The high pressure may not increase or may only increase slightly.
Possible deviation from specification |
Possible cause of fault |
Corrective
action |
- High and low pressure normal.
- Required cooling output is not attained
|
- Activation of A/C Compressor Regulator Valve -N280- is faulty.
- To much refrigerant oil in the circuit.
|
- Check activation of A/C Compressor Regulator Valve -N280-.
- Flush (clean) refrigerant circuit.
|
- High and low pressure normal.
- A/C compressor noise (particularly after switch-on).
- The required cooling performance is obtained
|
- To much refrigerant oil in the circuit.
|
- Discharge the refrigerant circuit.
- Flush (clean) refrigerant circuit.
- Charge the refrigerant circuit.
- Repeat the test.
|
|
|
|
Note
- Overfilling with refrigerant oil can occur if, for example, the
compressor has been replaced without adjusting the quantity of refrigerant
oil.
- If the A/C compressor is not replaced, the refrigerant oil should be
drained from the A/C compressor via the oil drain plug. Out of the entire
quantity of refrigerant oil, 50 grams should be put in the A/C compressor
and the rest in the refrigerant circuit. Refer to vehicle-specific repair
manual.
- If expansion valve is malfunctioning (permanently open), evaporator
temperature is no longer regulated such that only refrigerant in gaseous
state exits from the evaporator. Under certain usage conditions, liquid
droplets may then be drawn in by the compressor and cause noise (liquid
cannot be compressed).
With Expansion Valve, Receiver/Dryer and Electrically-Driven A/C
Compressor
Note
The electrically-driven A/C compressor does not have an A/C Compressor
Regulator Valve -N280-. The A/C compressor RPM does the regulating. The A/C
compressor contains the control electronics and a G-charger, which moves the
refrigerant.
Note
Connecting service station.
Observe test requirements.
Bring engine speed up to 2000 RPM.
Pay attention to the A/C service station pressure gauge.
Note
Switching pressures for actu ...
General Information
All components of the refrigerant circuit submitted for quality
observation are always to be sealed (use original sealing caps of original
part).
To date, the original parts ...
Volkswagen Tiguan Owners Manual
Volkswagen Tiguan Service and Repair Manual
© 2018-2025 Copyright www.vwtiguan.org - 0.1148